METAL-GRIP-FIRE-FENCE ø 244.5 - 457.2 mm

The original STRAUB fire protection system for applications where fire protection is required. The STRAUB FIRE-FENCE is the optimum solution for fire extinguishing equipment as well as for various systems with increased fire protection requirements such as in civil engineering (tunnels), for shipyards for seagoing vessels with various requirements and other applications. The STRAUB-FIRE-FENCE system is based on the standard types of the STRAUB-GRIP and STRAUB-FLEX series. In addition, an intumescent plastic is firmly bonded to the outside of the casing. In the event of fire, this swells and encloses the pipe coupling in a protective manner - while retaining full functionality.
Επιστροφή Τεχνικό Φυλλάδιο
adMm Clamping range [mm] PN industry [bar] PN shipbuilding [bar] B [mm] DV [mm] C [mm] X [mm] R without strip insert [mm] R with strip insert [mm] Torque rate [Nm] Allen head [mm] Thread metric
244.5 242.0 - 247.0 27 14 164 300 67 335 5 - 15 5 - 35 180 17 20
267 264.5 - 269.5 24 12 164 322 67 357 5 - 15 5 - 35 180 17 20
273 270.5 - 275.5 21 12 164 328 67 364 5 - 15 5 - 35 180 17 20
323.9 320.5 - 327.0 18 10 164 379 67 416 5 - 15 5 - 35 230 17 20
355.6 352.0 - 359.0 17 8 164 411 67 449 5 - 15 5 - 35 230 17 20
406.4 402.5 - 410.5 14 8 164 461 67 499 5 - 15 5 - 35 230 17 20
457.2 452.5 - 462.0 8 6 164 512 67 551 5 - 15 5 - 35 250 17 20
Remarks:
- Follow fitting instructions
- PN (Industry) = working pressure considering the application loads
- Test pressure = PN (Industry) x 1.5 (for example industry, water supply etc.)
- PN (Shipbuilding) = nominal pressure, includes four times safety factor (e.g. shipbuilding)
- The pressure values are valid on radial rigid carbon steel pipes under static loads
- Additional sealing sleeves and temperature ranges on request

STRAUB pipe couplings are made of the same or different materials depending on the diameter and size. The following overview shows the details. If you have any questions, please contact our application technology department.

Components W1 W2 W5
AISI A738, hot-dip galvanised - -
AISI 4135 - -
AISI 12L14, galvanised - -
AISI 301 - -
AISI 316 L or similar / PVDF - -
Sealing sleeve Temperatur Medium