TA SDR 11

Ταφ με ευθύ άκρο εξόδου μεγάλου μήκους

Ευθύς σύνδεσμος με εκτεθειμένες αντιστάσεις για βέλτιστη μεταφορά θερμότητας, μεγάλο βάθος διείσδυσης, ευρείες ζώνες συγκόλλησης και ζώνες ψύξης στις άκρες και στην μέση του εξαρτήματος για να αποτρέπεται η ροή λειωμένου υλικού, για χρήση χωρίς την ανάγκη μηχανισμών συγκράτησης.

Straight connector with exposed heating coils for optimal heat transfer, large insertion depth, wide fusion zones plus cold zones at the end and in the middle to prevent the flow of molten material, for use without holding devices. Up to and including d63 extra long outlet spigot dimensioned for 2 fusion operations.

Επιστροφή Τεχνικό Φυλλάδιο

PE 100 SDR 11

Maximum working pressure 16 bar (water)/10 bar (gas)

Κωδικός προϊόντος d BX PU D L1 t t1 z h B Weight kg
616685 20/20 200 3200 29 95 31 45 8 17 42 0,040
616338 25/25 50 900 36 110 41 66 13 19 54 0,080
615719 32/32 35 630 44 131 39 80 19 22 61 0,120
615720 40/40 20 360 53 151 43 88 30 25 70 0,210
615721 50/50 10 180 67 186 49 110 38 29 80 0,360
615722 63/63 10 180 81 203 56 125 42 33 94 0,530

FRIALEN safety fittings can be fused to pipes SDR11 - SDR 17.6. Minimum wall thickness s min ≥ 3 mm. Other SDR-stages on request. Please observe the marking directly at the product, which is mandatory. DVGW-Registration No.: DV-8601AU2248 and DV-8606AU2249.

Areas of Application

The FRIALEN-T pieces TA are used for pipe outlets of HD-PE pipelines.

Assembly Instructions

The fusion of the pipe ends with the FRIALEN-TA takes place by FRIALEN-fusing – leakproof and longitudinally strong.

The pipe ends are prepared (removing the oxide layer/cleaning) according to the general installation instructions (see “Assembly Instructions” for “FRIALEN-Safety Fittings for house connections and distribution pipes up to d 225”).

Good reasons for using the FRIALEN-TA:

Large coupler depth for ease of pipe guiding (no holding clamps required)

At dim. up to d 63, Length of outlet spigot dimensioned for two fusion operations

Extra wide fusion zones

Maximum stability through great wall thickness

Cold zones at the front side and in the middle of the coupler

Exposed heating coil for direct heat transmission to the pipe

Small annular gap for build-up of optimum joining pressure in the fusion zone

Touch proof electric contacts

Durable batch marking

Individually wrapped for dirt protection

Additional barcode for tracing back the fitting (Traceability-Coding)