Coupler without inner stop, SDR 11
Coupler UB SDR 11 without inner stop
- Gas, water and H2
- Working pressure: MOP (gas) 10 bar, PFA (water) 16 bar
- Material: PE 100
- Safety technology
- Large insertion depth for good pipe routing (no holding devices required)
- DVGW test mark: DV-8601AU2248, DV-8606AU2249, DV-8611AU2250 and DW-8610CN04200
- FM Approvals Class: 1613 (d 63 - d 500)
Note:
From nominal size 400 with separate fusion zone and preheating technology.
PE 100 SDR 11
Maximum permissible working pressure 16 bar (water) / 10 bar (gas)
Reference | d | BX | PU | D | L | t | h | B | Weight kg | |
---|---|---|---|---|---|---|---|---|---|---|
616577 | 16 | 135 | 4320 | 29 | 60 | 30 | 16 | 45 | 0,030 | |
612662 | 32 | 60 | 1920 | 45 | 77 | 39 | 21 | 61 | 0,070 | |
612663 | 40 | 40 | 1280 | 54 | 86 | 43 | 23 | 71 | 0,090 | |
612664 | 50 | 25 | 800 | 68 | 98 | 49 | 27 | 82 | 0,150 | |
612665 | 63 | 15 | 480 | 82 | 112 | 56 | 29 | 96 | 0,230 | |
612666 | 75 | 50 | 400 | 98 | 122 | 61 | 32 | 110 | 0,330 | |
612667 | 90 | 30 | 240 | 114 | 157 | 78 | 51 | 127 | 0,440 | |
612668 | 110 | 24 | 192 | 137 | 159 | 79 | 49 | 152 | 0,710 | |
612669 | 125 | 16 | 128 | 156 | 172 | 86 | 46 | 169 | 0,940 | |
615001 | 140 | 12 | 96 | 174 | 184 | 92 | 52 | 185 | 1,270 | |
612671 | 160 | 8 | 64 | 199 | 190 | 95 | 52 | 207 | 1,770 | |
612672 | 180 | 6 | 48 | 220 | 210 | 105 | 63 | 228 | 2,090 | |
612673 | 200 | 1 | 56 | 247 | 220 | 110 | 63 | 252 | 2,800 | |
612674 | 225 | 1 | 36 | 277 | 236 | 118 | 57 | 280 | 3,890 | |
617278 | 250 | 1 | 24 | 309 | 247 | 123,5 | 66 | 309 | 5,800 | |
617279 | 280 | 1 | 18 | 344 | 269 | 134,5 | 66 | 344 | 7,400 | |
1 | 612670 | 315 | 1 | 18 | 390 | 300 | 150 | 78 | 390 | 10,050 |
2 | 615074 | 355 | 1 | 9 | 445 | 300 | 150 | 68 | 445 | 14,600 |
615075 | 400 | 1 | 4 | 500 | 320 | 160 | 90 | 500 | 20,800 | |
615076 | 450 | 1 | 4 | 560 | 340 | 170 | 79 | 560 | 30,000 | |
615124 | 500 | 1 | 2 | 630 | 360 | 180 | 80 | 630 | 39,800 | |
616312 | 560 | 1 | 2 | 715 | 380 | 190 | 95 | 715 | 55,000 | |
616269 | 630 | 1 | 2 | 810 | 420 | 210 | 101 | 810 | 79,600 | |
616313 | 710 | 1 | 1 | 900 | 442 | 210 | 108 | 900 | 118,800 | |
616314 | 800 | 1 | 1 | 1000 | 500 | 250 | 136 | 1000 | 138,800 | |
616440 | 900 | 1 | 1 | 1130 | 600 | 300 | 165 | 1130 | 210,300 | |
616989 | 1000 | 1 | 1 | 1200 | 680 | 340 | 171 | 1200 | 121,000 |
Please note the mandatory labels directly on the product. DVGW test marks issued: DV-8601AU2248, DV-8606AU2249 and DV-8611AU22500.
Areas of Application
The FRIALEN-Coupler UB is used for cut and lay pipe connections.
Additional areas of application:
- Integration of adapters into an existing pipeline
- Connection of pipelines with fixed or restraint points
- Reinforcement / sealing of localised pipe damage
- Reinforcement of pinch points on small dimensions
Assembly Instructions
The fusion of pipe ends with the FRIALEN-Coupler UB takes place using FRIALEN-fusing – leakproof and longitudinally strong.
The pipe ends are prepared according to the general installation instructions (see “Assembly Instructions” for “FRIALEN-Safety Fittings for house connections and distribution pipes up to d 225” and “FRIALEN-Special Technology for laying large bore pipes and relining pipe networks”). This involves removing the oxide skin and cleaning the pipe ends. Please note that spigot of valves must be at least half as long as the coupler.
To compensate a larger annular gap (> 1 mm, max. 3 mm) between coupler and pipe, the pre-heating barcode can be used for couplers UB from d 400 (see instructions packed up with the coupler).
For removal of the oxide layer, FWSG scraper tools are available which facilitate a uniform swarf removal and a reproducible quality of the fusion area preparation.
Good reasons for using the FRIALEN-Slide-over Coupler UB:
- Large coupler depth for ease of pipe guiding (no holding clamps required)
- Extra wide fusion zones
- Maximum stability through great wall thickness
- Cold zones at the front side and in the middle of the coupler
- Exposed heating coil for direct heat transmission to the pipe
- Small annular gap for build-up of optimum joining pressure in the fusion zone
- Touch proof electric contacts
- Fusion indicators for visual fusion control
- From d 400: pre-heating technique for a optimal gapbridging
- From d 400: External reinforcement for an ideal fusion pressure
- Durable batch marking
- Individually wrapped for dirt protection
- Additional barcode for tracing back the fitting (Traceability-Coding).