FCZ

Gasket NBR, DIN-EN 682 MOP gas according to table, maximum = 5 bar Other water qualities according to table, maximum = 16 bar

Two-piece repair clamp for sealing damaged gas and water pipes made of different materials (steel, cast iron, ductile iron, asbestos cement, PVC).

  • Special gasket design for a secure sealing of tapping holes, cracks and corrosion damage
  • Body, closure, bolts and nuts made of stainless steel
  • Gasket material EPDM or NBR
Go back Data sheet

Gasket NBR, DIN-EN 682

MOP gas according to table, maximum = 5 bar

Other water qualities according to table, maximum = 16 bar

Reference d PN BX PU SW Weight [kg]
382-088-200 88-110 5 6 192 17 2,620
382-088-300 88-110 5 6 144 17 4,000
382-088-400 88-110 5 6 96 17 7,490
382-100-300 100-120 5 4 144 17 5,740
382-108-200 108-128 5 4 128 17 2,740
382-108-300 108-128 5 4 96 17 4,170
382-108-400 108-128 5 4 64 17 5,460
382-114-300 114-134 5 4 96 17 4,270
382-120-200 120-140 5 4 128 17 2,970
382-130-200 130-150 5 3 64 19 3,510
382-130-300 130-150 5 3 48 19 5,350
382-140-200 140-160 5 3 64 19 3,610
382-140-300 140-160 5 3 48 19 6,260
382-159-200 159-180 5 2 64 19 3,740
382-159-300 159-180 5 2 48 19 6,520
382-159-400 159-180 5 2 16 19 8,760
382-168-300 168-189 5 2 48 19 6,620
382-190-200 190-210 5 2 64 19 5,900
382-210-200 210-230 5 1 32 19 6,600
382-210-300 210-230 5 1 24 19 6,810
382-218-300 218-238 5 1 24 19 6,970
382-218-400 218-238 5 1 16 19 10,060
382-269-300 269-289 5 1 24 19 7,570
382-269-400 269-289 5 1 16 19 10,890
382-315-300 315-335 5 1 24 19 8,080

Areas of application

FRIACLAMP repair clamps for secure sealing of damaged pipes made of different materials (steel, cast iron, ductile iron, asbestos cement, PVC). Available from DN 40 to DN 300. Also available in one-piece design.

FRIACLAMP repair clamps can be used with the standard NBR gasket for gas, water and wastewater.

Processing instructions

FRIACLAMP can be used to reliably seal damaged pipes. The installation length of the repair clamp should be selected so that it corresponds at least to the outside diameter of the pipe to be repaired.

The pipe surfaces must be prepared in accordance with the general installation requirements (see FRIACLAMP installation instructions).

* Permissible operating pressure:

Gas: Permitted operating pressure 5 bar (≤ DN 300).

Water: Permitted operating pressure:

≤ DN 200 PN 16

> DN 200 PN 10

> DN 300 on request.

Good reasons for FRIACLAMP

  • Quick locking System with Nuts and Bolts in V2A
  • No welded parts
  • Seal with large unique profile
  • Dovetail-shaped sealing webs form sealing lips when pressed against the pipe surface
  • Secure sealing even on corroded pipe surfaces
  • No sharp edges
  • No loose parts when opening the one-piece and two-piece repair clamps enable time-saving installation
  • Movable handle ensures easy installation with minimum installation space requirements
  • Optimized locking mechanism ensures defined pretensioning of each bolt
  • Assembly possible with standard tools

Downloads