Tapping ball valve for side tapping gas under pressure
Tapping ball valve AKHP for gas
- Gas and H2
- Working pressure: MOP (gas) 10 bar
- Material: PE 100
- Gasket: NBR
- 1/4 turns for opening and closing
- Saddle component with clamp
- Safety technology
- DVGW test mark: DG-8631AU2252 and DG-8631AU2253
Note:
For this purpose, there is a suitable actuating linkage KBS for wrench sizes SW14 (14 mm) and SW30 (30 mm ).
For tapping under pressure, we recommend the tapping tool from Hütz & Baumgarten (www.huetz-baumgarten.de).
Areas of Application
The FRIALEN-Tapping Ball Valve, completely made from HD-PE, makes it possible to tap sideways into an operational HD-PE mains under gas and water pressure (no drinking water!) – without any escape of gas or water.
Assembly Instructions
The fusion of FRIALEN Tapping Ball Valves to the HD-PE main takes place by FRIALEN fusing – leakproof and longitudinally strong. The pipe and the saddle have to be prepared (oxide layer removal/cleaning) in accordance with the general installation instructions (see „Assembly Instructions“ for FRIALEN Safety Fittings for house connections and distribution pipes up to d 225).
Tapping of the HD-PE pipe under operating pressure
For this we recommend the tapping equipment of Hütz + Baumgarten. It is clamped onto the exposed fusion end of the ball valve. The tapping of the HD-PE pipe takes place through the opened ball valve and is leakage free.
Actuating the shut-off valve
By the telescopic actuating installation kit KBS from the valve cover.
Good reasons for using the FRIALEN-Tapping Ball Valves:
- Fusioning and tapping under pressure saves time-consuming and expensive shut-offs and emergency supply during the integration
- Installation of mains and service lines takes place on one level and thus affords advantages in the planning stages
- Construction and connecting works are reduced to a minimum
- The ball valve can be used as a shut-off device afterwards
- Additional barcode for tracing back the underground fitting (Traceability-Coding)